Publication 1794-UM062A-EN-P - September 2012

26

Install Your FLEX I/O Module

Chapter Summary

In this chapter you learned how to install the FLEX I/O analog module in an
existing programmable controller system and how to wire to a terminal base unit.

Wire Connections for 1794-TB3S, 1794-TB3T and 1794-TB3TS using the 1794-IE4XOE2XT Module

Channel

Signal
Type

Label
Markings

1794
-TB3S,
-TB3T,
-TB3TS

1794-TB3S

1794-TB3S 1794-TB3T,

1794-TB3TS

Input/Output
Terminal

(1)

Power
Terminal

(2)

Common Terminal

Shield

Input 0

Current

I

A-0

C-35

B-17

B-17

C-39

Voltage

V

A-1

C-36

B-18

Input 1

Current

I

A-2

C-37

B-19

B-18

C-40

Voltage

V

A-3

C-38

B-20

Input 2

Current

I

A-4

C-39

B-21

B-21

C-41

Voltage

V

A-5

C-40

B-22

Input 3

Current

I

A-6

C-41

B-23

B-23

C-42

Voltage

V

A-7

C-42

B-24

Output 0

Current

I

A-8

C-43

Voltage

RET

A-9

V

A-10

C-44

RET

A-11

Output 1

Current

I

A-12

C-45

Voltage

RET

A-13

V

A-14

C-46

RET

A-15

24V DC
common

1794-TB3S – Terminals 16…33 are internally connected in the terminal base unit.
1794-TB3T, 1794TB3TS- – Terminals 16, 17, 19, 21, 23, 25, 27, 29, 31 and 33 are internally
connected in the terminal base unit.

+24V DC
power

1794-TB3S – Terminals 34…51 are internally connected in the terminal base unit.
1794-TB3T, 1794-TB3TS – Terminals 34, 35, 50 and 51 are internally connected in the terminal
base unit.

Chassis
ground
(Shield)

1794-TB3T, 1794-TB3TS – Terminals 39…46 are internally connected to chassis ground.

(1)

A-9, 11, 13 and 15 are internally connected in the module to 24V DC common.

(2)

Use when transmitter requires terminal base power.