Publication 1794-UM062A-EN-P - September 2012

74

Module Programming

The two’s complement of 0 is not found, since no first ”1” is ever encountered in
the number. The two’s complement of 0 then is still 0.

Analog Data Format

The data returned from the analog-to-digital converter in the module is 12-bit
resolute. This value is left-justified into a 16-bit field, reserving the most
significant bit for a sign bit.

Current and Voltage Mode Values

Current (mA) 4…20 mA Mode 0…20 mA Mode Voltage (V)

± 10V Mode

0…10V Mode

Input

Output

-10.50

8000

8000

0.00

0000

-10.00

8620

8618

1.00

0618

-9.00

9250

9248

2.00

0C30

-8.00

9E80

9E78

3.00

1248

-7.00

AAB0

AAA8

4.00

0000

1860

-6.00

B6E0

B6D8

5.00

0787

1E78

-5.00

C310

C310

6.00

0F0F

2490

-4.00

CF40

CF40

7.00

1696

2AA8

-3.00

DB70

DB70

8.00

1E1E

30C0

-2.00

E7A0

E7A0

9.00

25A5

36D8

-1.00

F3D0

F3D0

10.00

2D2D

3CF0

0.00

0000

0000

0000

11.00

34B4

4310

1.00

0C30

0C30

0C30

12.00

3C3C

4928

2.00

1860

1860

1860

13.00

43C3

4F40

3.00

2490

2490

2490

14.00

4B4B

5558

4.00

30C0

30C0

30C0

15.00

52D2

5B70

5.00

3CF0

3CF0

3CF0

14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

11 10 09 08 07 06 05 04 03 02 01 00

S

S

14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

10 09 08 07 06 05 04 03 02 01 00

S

S

14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

11 10 09 08 07 06 05 04 03 02 01 00

0*

A/D unipolar data

A/D bipolar data

D / A d a t a

Output

Input

A n a l o g v a l u e

A n a l o g v a l u e

A n a l o g v a l u e

*

= A l w a y s p o s i t i v e

xxxxx