Communicate With Your Module 33

The adapter input status word bit descriptions are shown in table Word Bit
Description on page 33.

Possible causes for an I/O module fault are:

• transmission errors on the FLEX I/O backplane
• a failed module
• a module removed from its terminal base
• incorrect module inserted in a slot position
• the slot is empty

The node address changed bit is set when the node address switch setting has
been changed since power up. The new node address does not take effect until
the adapter has been powered down and then powered back up. Until this power
cycling occurs, the node address switches will not match the actual node address.

Defaults

Each I/O module has default values associated with it. At default, each module
generates inputs/status and expects outputs/configuration.

Word Bit Description

Bit Description

Bit

Explanation

I/O module fault

0

This bit is set (1) when an error is detected in slot position 0.

1

This bit is set (1) when an error is detected in slot position 1.

2

This bit is set (1) when an error is detected in slot position 2.

3

This bit is set (1) when an error is detected in slot position 3.

4

This bit is set (1) when an error is detected in slot position 4.

5

This bit is set (1) when an error is detected in slot position 5.

6

This bit is set (1) when an error is detected in slot position 6.

7

This bit is set (1) when an error is detected in slot position 7.

Node address
changed

8

This bit is set (1) when the node address switch setting has
been changed since power up.

I/O state

9

Bit = 0 – idle
Bit = 1 – run

10…15 Not used – sent as zeroes.

Module Default Values

Module Defaults for:

Factory Defaults

Real Time Size

Catalog
Number

Description

Input
Default

Output
Default

Input
Default

Output
Default

1794-IE8/B

8-pt Analog Input

9

6

8

0

1794-IE8XT

8-pt Analog Input

9

6

8

0

1794-IE12

12-pt Analog Input

13

2

12

1

1794-OE4/B

4-pt Analog Output

1

14

0

4

Advertising