Data Tables 65

Write word 4

Bits 00…14
(00…16)

Channel 3 analog data – 12-bit left justified two's
complement number; unused lower bits are zero;
4…20 mA uses all 16 bits.

Bit 15 (17)

Channel 3 analog data sign bit.

Write word 5

Bits 00…11
(00…13)

Configuration – Set the 2 bit pattern that configures
a pair of channels for Off, 0…20 mA, 4…20 mA, and

±10V. For more information, see

Table Range

Selection Bits – 1794-IE8XOE4 Analog Combo Module
on page 63

.

Bits 12…14
(14…16)

Set to 0.

Bit 15 (17)

Quick Step bit – Set to 1 to allow input filter to be
reduced during rapid signal changes. Ince the signal
change is within 1% of FS (that is, 327 counts),
filtering is returned to normal.