7Ć6

AutoMax Programming Executive Version 3.x

In order for application tasks in the rack to be able to access the

variable in this rack, the register/bit must have a local name in the

rack. The local name for a register/bit will be displayed (in the local

name" field) only when configuring the Network module that contains

the actual drop area where the register/bit is located. The local name

will not be displayed in this register/bit location when the Network

drop area is viewed through any other Network module on the

network. Note that the meaning of local" in terms of the Network

module configuration form is different from local" in the sense of

variable access in a single application task as described in

section 7.1.
To add a networkĆwide name to a rack configuration so that

application tasks within the rack can access it, the networkĆwide

name must be linked to a local name. This is done by checking the

Link networkĆwide and local variable names/descriptions" checkbox

when the desired networkĆwide name is selected. Note that whether

the local or networkĆwide names are linked or not, only the

networkĆwide description will be displayed on the form. The local

description will be displayed in the default fields at the bottom of the

screen when the register is selected.
If you link the networkĆwide and local variable names when the local

name field is empty, the networkĆwide name will be copied to the

local name field. Conversely, if the local name is specified and the

networkĆwide field is empty, checking the box will copy the local

name to the networkĆwide field. NetworkĆwide and local names doe

not have to be the same in order to be linked. When the names are

linked, the Linked" column on the screen will display a

doubleĆheaded arrow (<-->). If you delete a networkĆwide variable

name, any local variables linked to that name will also be deleted for

all racks in the system.
Because of the way in which linked networkĆwide names are stored

(in the network database as well as in individual rack configurations),

there is a great deal of flexibility in manipulating the configuration of

the network. You can edit or copy linked networkĆwide names from

any Network module on that network. Linking the local name to the

networkĆwide name is also helpful in case you need to reĆorganize

your use of network registers because all local names linked to a

networkĆwide name are copied when the networkĆwide name is

copied. Further, if you edit the networkĆwide name for a register, the

new name will replace the old networkĆwide name for all racks on the

network. It is important, however, to understand the results of editing

a linked networkĆwide name.
In order to successfully edit, i.e., change the name of a linked

networkĆwide variable, the rack configuration databases for all the

racks on the network must be present and accessible so that the

AutoMax software can change the name in each at the same time.

The reason for this is that when the configuration object code for a

rack is generated, the actual register/bit address of a linked local

name is determined using the networkĆwide name, which is also

stored in the rack's database, as a key into the network database. If a

register/bit has a local name which is NOT linked to a networkĆwide

name, the register/bit address is found in the rack database, not the

network database. If the change cannot be made in all of the racks'

databases at this time, the old networkĆwide name (in the unchanged

rack's database) will no longer have a corresponding entry in the

network database. This condition will be flagged as an unresolved

networkĆwide name" when the configuration for this rack is

generated.