On Line Menu: Monitoring and Editing Tasks

18.2.2 Displaying I/O Registers

You can display up to 16 registers on the screen at one time. The

Monitor I/O screen display is described in 18.2.1. To display a

register on the screen, follow the directions below:
1. Enter D" for Display" from the Monitor I/O menu shown in

figure 18.5.

2. If the register you want to display is in the local rack, enter L" for

Local and go on to the section entitled Displaying Local I/O". If

the register is in a remote rack, enter R" for Remote and go on

to the section entitled Displaying Remote I/O".

18.2.2.1

Displaying Local I/O
a. Enter the slot number of the module on which the register is

found.

b. Enter the register number.
c. Select the format of the display in the Value" field as follows:

D" for decimal

H" for hexadecimal

B" for binary

d. Type Enter" or <CR> to display the register.

18.2.2.2

Displaying Remote I/O
a. Enter the slot number of the Remote I/O master module (M/N

57C416) in the local rack.

b. Enter the drop number of the remote chassis in which the

module containing the register is located.

c. Enter the slot number of the module in the remote rack that

contains the register.

d. Enter the register number.
e. Select the format of the display in the Value" field as follows:

D" for decimal

H" for hexadecimal

B" for binary

f. Type Enter" or <CR> to display the register.