KĆ2

AutoMax Programming Executive Version 3.x

DCS Drive Controller (M/N 57406) Example

The registers listed below are used to configure the DCS Drive Controller.

Current Version

AutoMax V2

Executive AutoMax

RegisterBit

RegisterBit

Function

1

4096

Analog Reference Input

2

4097

Analog Tach Feedback

3

4098

Armature Voltage Feedback

4

4099

Major Loop Current FDBK

5

4100

AC Line Voltage FDBK

41

4136

Tach Loss Delta Threshold

42

4137

PLL Max. Phase Change

43

4138

PLL Max. Period Change

51

0

4146

0

Fast Bridge Change Enable

Note that the register numbers used in the current version correspond to the old

register numbers plus 4095. Before executing the Import procedure, edit your

AutoMax V2 configuration task to set the register numbers for this module to their

new values by adding 4095 to each register number used for this module.