Rockwell Automation 57C650 AutoMax Programming Executive Version 3.8 User Manual

Page 247

Advertising
background image

FĆ3

Database Definitions

For the Shark Scanner module

(M/N 57C554), the value is one (1) for an

allĆdigital rack or zero (0) for a mixed rack.

WIRE_NOTE2 NUMERIC

For AutoMax Processors (M/N 57C430A,

57C431, and 57C435), the low order byte of

the AutoMax Processor tick rate (in

microseconds)
For the UDC module (B/M 57552 and

B/M 57652), the drive type for drive B

(see Parameter Record Types table for

values)

Note: Memory variables are stored in slot 99.

Database: $SWVAR.DBF and $NET.DBF
FIELD

TYPE

DESCRIPTION

MAST_SLOT

NUMERIC

The slot in the master rack which contains

this card or which contains the remote I/O

card which is the remote I/O network

master (00Ć15)

REM_DROPNUMERIC

If this card is in a remote rack, this is the

drop number for that remote rack (1Ć7);

otherwise, it is 0

SLOT

NUMERIC

The slot in which the variable resides

(00Ć15)

REGISTER

NUMERIC

The multibus register number (0Ć65535)

BIT

NUMERIC

The bit number within the multibus register

for boolean variables (0Ć15)

LVAR_NAME

CHARACTER

The variable without type specifier or array

dimensions; for network variables, this is

the local variable name

GVAR_NAME CHARACTER

The variable without type specifier or array

dimensions; used for the networkĆwide

name for network variables only

NETWORK

CHARACTER

Network identifier; used for network

variables only (AĆZ)

DESC

CHARACTER

The description of this variable

ARRAY_DIM1 NUMERIC

First dimension; used for memory

variables only

ARRAY_DIM2 NUMERIC

Second dimension; used for memory

variables only

ARRAY_DIM3 NUMERIC

Third dimension; used for memory

variables only

ARRAY_DIM4 NUMERIC

Fourth dimension; used for memory

variables

DATA_TYPE

NUMERIC

The type of this variable:

ăă8

Floating point

ă16 !

Double integer

Advertising