AutoMax Programming Executive Version 3.x

EA

Error installing application task, common symbol could not be

resolved, insufficient memory in Processor Module. I/O referenced

in configuration is missing.

Eb

Error installing application task, common symbol could not be

resolved, insufficient memory in Processor Module. I/O referenced

in configuration is missing. Invalid configuration, configuration not

successfully downloaded.

EC

Error building task; and error installing application task, common

symbol could not be resolved, insufficient memory in Processor

Module.

Ed

Error building task; and error installing application task, common

symbol could not be resolved, insufficient memory in Processor

Module. Invalid configuration not successfully downloaded.

EE

Error building task; and error installing application task, common

symbol could not be resolved, insufficient memory in Processor

Module. I/O referenced in configuration is missing.

EF

Common variable forced by another Processor Module.

Corrective action: verify that the configuration correctly describes the physical

configuration of the system and the tasks installed on the Processor module(s).

Reset by cycling power and reĆloading the configuration and application tasks.

For error code EF, unĆforce the variable and do a STOP ALL from the AutoMax

ON LINE PROGRAMMING menu.

Fatal Errors

The following error codes usually indicate that the runbase is not functioning

correctly. If any of these error codes appears, the configuration and all application

tasks are deleted from the Processor module.
F0ĆF9

Fatal error

FAĆFF

Fatal error

Corrective action: cycle power. ReĆload the configuration and all application

tasks. Replace the Processor module.

Informational Messages

The following codes signify a particular condition, not necessarily an error.
dd

This Processor module has successfully

completed powerĆup diagnostics and is waiting for

other Processor modules to complete their

diagnostics

L0

The runbase needs to be loaded onto the rack

b0

Rack configuration is being validated

d0

Application task installation in progress

d1

Waiting on synchronizing event (in a rack with

multiple Processors)

d2

Waiting on mutual exclusion lock (in a rack with

multiple Processors)

Corrective action for b0 and d0 that do not change or disappear: reĆload

configuration and application tasks.