AutoMax Programming Executive Version 3.x

when a STOPĆALL command is issued by the operator or the system

issues a STOPĆALL. To stop all tasks in the rack, follow the directions

below:
1. From the ON LINE menu, select S" for Stop.
2. The screen will display No task selected" and the option All".

Enter A" to stop all tasks. The Status" field for all tasks will then

show that the tasks are in STOP.

Table 16.1Ć Status of Data in the AutoMax Rack after a

STOPĆALL Command or STOPĆALL Fault

AutoMax

Processor

UDC Module

PMI

Processor

LOCAL tunable variables

retained

retained

retained

LOCAL variables

retained

reset to 0

N/A

COMMON memory variables

nonĆvolatile

are retained;

others are

reset to 0

N/A

N/A

I/O variables (including UDC

dual port memory)

inputs

retained and

updated;

outputs are

reset to 0

inputs

retained and

updated;

outputs are

reset to 0

all I/O is

reset to 0

Input values, including:

Feedback registers

UDC/PMI communication

status registers

UDC Error Log info

retained

retained

N/A

Output values, including:

Command registers

Application registers

ISCR registers

ScanĆperĆinterrupt register

ScansĆperĆinterrupt counter

reset to 0

reset to 0

N/A

Parameter configuration

variables

N/A

retained

N/A

UDC test switch information

N/A

retained

N/A

D/A setup configuration

N/A

retained

N/A

Operating system

retained

retained

retained