Processor Module Error and Status Codes

AutoMax DriveĆRelated Error Codes

The following error codes indicate a power circuit or external drive system fault.

They apply only to systems that incorporate DCS 5000 microĆregulators. After

correcting the problem, reset the Processor module by cycling power and

reĆloading the configuration task and application tasks to clear the error code.

Note that these error codes also appear in the Error Log for the Processor.
80

Instantaneous overcurrent fault

Ć armature current exceeded IOC_THRESH

value in CML task

81

Line sync loss fault

82

Tach loss fault

Ć 40% armature phase angle with less than 5% tach

feedback

83

Overspeed/overvoltage fault

Ć CML task OSV_FDBK exceeded OSV_THRESH

number

84

Hardware overspeed fault

Ć drive analog module potentiometer setting

exceeded by input voltage

85

External IET fault

Ć external fault input triggered

86

Phase rotation fault

Ć incorrect phasing

87

Shorted SCR detected in power module

Corrective action: troubleshoot power circuit and external drive system. These

errors do not cause a Stop All and do not require reĆloading the configuration or

application tasks.

Configuration Error Codes

The following error codes usually indicate a discrepancy between the actual

hardware configuration and the I/O definitions in the configuration for the rack.
E0

TASK specified in configuration uninstalled,

at wrong priority, of wrong type, on wrong

Processor module; wrong spelling of TASK

E1

Invalid configuration, configuration not successfully downloaded.

E2

I/O referenced in configuration is missing.

E3

I/O referenced in configuration is missing. Invalid configuration,

configuration not successfully downloaded.

E4

Error building task, insufficient memory in Processor Module.

Invalid configuration, configuration not successfully downloaded.

E5

Error building task, insufficient memory in Processor Module.

Invalid configuration, configuration not successfully downloaded.

E6

I/O referenced in configurations is missing. Error building task,

insufficient memory in Processor Module.

E7

Invalid configuration, configuration not successfully downloaded.

I/O referenced in configuration is missing. Invalid configuration,

configuration not successfully downloaded.

E8

Error installing application task, common symbol could not be

resolved, insufficient memory in Processor Module.

E9

Error installing application task, common symbol could not be

resolved, insufficient memory in Processor Module. Invalid

configuration, configuration not successfully downloaded.