BĆ4

AutoMax Programming Executive Version 3.x

BASIC STOP ALL Error Codes

The following error codes are caused by problems in BASIC tasks and cause all

tasks to stop.
40

Too many RETURNs from GOSUBs (or RETURN

without GOSUB)

41

Illegal jump into a FOR loop

42

NEXT statement does not match current FOR

43

Invalid START EVERY statement

44

Invalid EVENT statement

45

STOP statement executed in application software

(causes a STOP ALL/CLEAR)

46

SET or WAIT attempted with no event definition

47

Task stack overflow

48

GOSUBs not balanced at END statement

49

Insufficient space for channel buffer

4A

Attempted to execute undefined opcode

4B

Attempted to execute nonĆexecutable opcode

4C

Attempted to execute illegal opcode

4D

RESTORE to nonĆDATA statement line number

4E

Attempted to take square root of a negative

number

4F

Attempted RESUME without being in an ON

ERROR handler

Corrective action: correct the problem in application software. Error code 47 can

be caused by performing a PUT on a closed port, PRINT statements, GOSUB

without RETURN, and deeplyĆnested subroutines. Error code 4A can be caused

by attempting to use Ethernet functions with the standard operating system

loaded. To use Ethernet functions, you must load the Ethernet operating system.

MultibusT and Processor Bus

STOP ALL Error Codes

50

Onboard parity error

51Ć54

Onboard bus error or access violation

55

Multibus parity error during read access

56Ć58

Multibus access violation or bus error

60

Network interrupt allocation failed

61

Network receiving queue overflow

62

Network transmit queue underflow

Corrective action: reset by cycling power and reĆloading configuration and

application tasks. If the small green LED labeled OK" on the Processor module

faceplate is off, replace the Processor module. Correct any incorrect accesses in

application software. Systematically swap out hardware modules. For error codes

55Ć58, if none of the above correct the problem, try replacing the backplane.