Rockwell Automation 57C650 AutoMax Programming Executive Version 3.8 User Manual

Page 161

Advertising
background image

11Ć3

AutoMax On Line Menu

Release

ON LINE direct

C: \LIB\SYS\RACK

Auto Run

F3ăExit

Direct

Set Access

Userlist

F1ăHelp

Baud Rate

Network

Config NORMAL

Keysw Program

Access

Task

Auto Run

DISABLED

Slot Task ăăăă

Type ăăPri R C M A Status

Slot Task

ăăăăăăăăăType Pri R C M A Status

"1

BASTEST

Bas

4 R C

RUN

1

BASTEST1

Bas

4

Stop

1

BASTEST2

Bas

4

C

Stop

1

BASTEST3

Bas

5 R

Stop

1

BASTEST4

Bas

6

C

Stop

1

BASTEST5

Bas

7

Stop

1

BASTEST6

Bas

8 R C

Stop

1

BASTEST7

Bas

9

Stop

1

BASTEST8

Bas

10 C

Stop

1

BASTEST9

Bas

4 R

Stop

1

INITDACS

Bas

11

Stop

1

PCCOILS

PC

11R

Stop

1

PCTESTV5

PC

11R C

Stop

Figure 11.2 ĆON LINE Menu Display with Task Running

The top status line displays general information about the rack. The

Config" field shows whether the NORMAL or DEBUG version of the

rack configuration has been loaded to the rack. If the rack

configuration has not been loaded, NONE" wll be displayed. The

keyswitch position, Program in this case, is shown in the Keysw"

field. The Forced" field, when shown, indicates whether there are

any forced variables in the rack. See 18.5 for more information on

forcing.
The user's access level is displayed in the field Access" as None,

Data, Rack, Locked, or, as shown here, Task". Auto Run" is either

enabled" or as shown here, Disabled". See 12.4 for more

information about AUTOĆRUN.
The second status line displays specific information about tasks in

the rack. Slot" denotes the AutoMax Processor or UDC module on

which the task is running. Task" is the name of the task and Type"

denotes the programming language (.BLK, .BAS, or .PC).
Pri" is the task's priority as defined in the configuration for the rack.

The priority ranges from 4 (highest) to 11 (lowest). UDC tasks do not

display a priority. A" is displayed for Drive A tasks; B" is displayed

for Drive B tasks. See Appendix C for more information on task

priority. The field R" will show an R if the task is reconstructible. See

8.1.1 for more information about the /Reconstruct option used in

compiling tasks.

Advertising