Rockwell Automation GV3000/SE V.6 Regulator Board 0-56921-6xx, 413338-6BU, 0-56940-6xx, 814.61.00 User Manual

Page 14

Advertising
background image

2-2

GV3000/SE Drive Version 6 Regulator Board Installation Instructions

Refer to figure 2.2 as you perform the procedure.

Important: Read and understand the warning labels on the outside of the drive

before proceeding.

Step 1.

Shut Down the Drive

Step 1.1. Disconnect, lock out, and tag all incoming power to the drive.

Step 1.2. Wait five minutes for the DC bus capacitors to discharge.

Step 1.3. Remove the cover by loosening the four cover screws.

Important: Read and understand the warning labels on the inside of the drive before

proceeding.

Step 2.

Verify That the DC Bus Capacitors are Discharged

Step 2.1. Use a voltmeter to verify that there is no voltage at the drive’s AC input

power terminals (R/L1, S/L2, T/L3).

Step 2.2. Ensure that the DC bus capacitors are discharged. To check

DC bus potential:

a. Stand on a non-conductive surface and wear insulated gloves.

b. Use a voltmeter to measure the DC bus potential at the DC bus power

terminals as shown in figure 2.1.

Step 3.

Remove the Keypad Bracket from the Drive

Step 3.1. Record the wiring to the Regulator board terminal strip.

Step 3.2. Disconnect the wiring from the Regulator board terminal strip.

Step 3.3. Drives with option boards only: Record the wiring connections to the option

board terminals. Disconnect this wiring from the option board terminal strip.

Figure 2.1 – DC Bus Voltage Terminals (1 to 5 HP @ 460 VAC Drives)

!

ATTENTION: The drive contains printed circuit boards that are
static-sensitive. An anti-static wristband should be worn by any person
who touches the drive components, connectors, or wiring. Erratic
machine operation and damage to, or destruction of, equipment can
result if this precaution is not followed.

W/T3

V/T2

U /T1

+

S/L2

1 0V

1 0 COM

Motor Leads

AC Power

Input Leads

DC Bus

Volts

R/L1

T/L3

+

Advertising