Restoring the Drive Configuration

12-1

C

HAPTER

12

Restoring the Drive Configuration

After the Regulator board has been replaced, the drive powers up with the parameters
set to their factory-default values. If you changed any of the parameters from their
default values prior to replacing the board, you must change them again after you
have completed the Power Module identification procedure described in chapter 11.

Use one of the following methods to restore your configuration:

If you have purchased the Control and Configuration Software (CS3000) and
saved your configuration to your personal computer prior to replacing the
Regulator board, you can use the CS3000 software to load the configuration to
the new Regulator board. Refer to the CS3000 instruction manual (D2-3348) for
this procedure.

If you are using the keypad to configure the drive and you have a record of the
changes made to the parameter settings, you need to change only those
parameters affected. Refer to the software reference manual for parameter
descriptions.

If you are using the keypad to configure the drive and you have no record of
changes made to the parameters, you need to perform the appropriate start-up
procedure in the software reference manual.

Important: For drive M/N 30R41xx, 30T41xx, 50R41xx, 75R41xx, 75T41xx, and

125R41xx configured for V/Hz control, the Identification Request
procedure (initiated using parameter H.020) must be performed after the
configuration has been restored. Refer to the H.020 parameter
description in the software reference manual for information about this
procedure.