Installing Regulator Board P/N 0-56921-6xx in 15 to 25 HP and 25 to 60 HP @460 VAC Drives

6-3

Step 2.

Verify That the DC Bus Capacitors are Discharged

Step 2.1. Use a voltmeter to verify that there is no voltage at the drive’s AC input

power terminals (R/L1, S/L2, T/L3).

Step 2.2. Ensure that the DC bus capacitors are discharged. To check

DC bus potential:

a. Stand on a non-conductive surface and wear insulated gloves.

b. Use a voltmeter to measure the DC bus potential at the DC bus power

terminals as shown in figures 6.3 (15 to 25 HP) and 6.4 (25 to 60 HP).

Figure 6.2 – Regulator Board Location in 25 to 60 HP @ 460 VAC Drives

Option Board

Regulator Board

Front View

Top View

Figure 6.3 – DC Bus Voltage Terminals (15 to 25 HP @ 460 VAC Drives)

Motor Leads

AC Power

Input Leads

DC Bus

Volts

+

V/T2

U/T1

T/L3

S/L2

R/L1

W/T3