Rockwell Automation GV3000/SE V.6 Regulator Board 0-56921-6xx, 413338-6BU, 0-56940-6xx, 814.61.00 User Manual

Page 53

Advertising
background image

7-6

GV3000/SE Drive Version 6 Regulator Board Installation Instructions

Step 5.5. Drives with option boards only: Remount the option board to the keypad

bracket using the four screws removed earlier.

Step 5.6. Route the new Regulator board’s 60-conductor ribbon cable through the

slot in the hinged mounting panel to the connector on the Power Unit
Interface board. Align the two connectors. Placing your thumb beneath the
Power Unit board for support, carefully press the ribbon cable connector in
until it locks into position.

Step 6.

Reinstall the Keypad Bracket in the Drive

Step 6.1. Reattach the keypad bracket to the hinged mounting panel using the four

screws and lock washers removed earlier.

Step 6.2. Connect the green-striped keypad ribbon cable to the new Regulator board.

Align the ribbon cable connector with the Regulator board connector and
carefully push the keyboard cable in until it snaps into place. Verify that it is
locked into position by gently tugging on the cable.

Step 6.3. Swing the hinged mounting panel back up into position. Make certain that

the keypad ribbon connector is tucked into the cabinet and not pinched by
the panel. Refasten the two screws to the top of the panel.

Step 6.4. Drives with option boards only: Connect the option board wiring to the

appropriate option board terminals. Route the cables through the right-most
wire-routing hole at the bottom of the drive, away from the AC lines.

Refer to the terminal connections documented earlier or to the appropriate
instruction manual for the option board that is being used.

Step 6.5. Connect all Regulator board wiring to the appropriate terminals on the

Regulator board terminal strip. Route the wiring through the right-most
wire-routing hole at the bottom of the drive, away from the AC lines.

Refer to the terminal connections documented earlier or to the appropriate
instruction manual for the devices being used.

Step 6.6. Replace the two screws at the top of the hinged panel on which the keypad

bracket is mounted.

Step 6.7. NEMA 4X/12 drives only: Before installing the cover, check that the gaskets

on the cover are flat and within the gasket channels.

Step 6.8. Reinstall the cover. Align all cover screws into the heat sink before

tightening any of them. Make certain that no wires or cables are being
pinched by the cover.

To maintain the integrity of NEMA 4X/12 drives, sequentially tighten the
cover screws to ensure even compression of the gaskets. Do not exceed
2.2 Nm (20 in-lb) of torque on these screws.

Step 6.9. Remove the lockout and tag. Apply power to the drive. SELF is displayed

while the drive performs power-up diagnostics. When diagnostics are
complete, the fault code CHS will be displayed.

This completes the hardware installation of the Regulator board replacement
procedure. Go to chapter 11 for the procedure to clear the CHS fault code.

Advertising