Rockwell Automation GV3000/SE V.6 Regulator Board 0-56921-6xx, 413338-6BU, 0-56940-6xx, 814.61.00 User Manual

Page 37

Advertising
background image

Installing Regulator Board P/N 0-56921-6xx in 30 to 100 HP @ 230 VAC and 75 to 200 HP @ 460 VAC Drives

5-5

To remove a plastic rivet, pull the post from the rivet body. Remove the body
of the rivet. Use a small pair of wire cutters or a similar tool to pry these
pieces loose. Do not cut the rivets.

Step 4.3. Drives with option boards only: Remove the Regulator board ribbon

connector from the option board. The connector is held in place by retaining
clips. Spread these clips to release the connector.

Step 4.4. Slide the old Regulator board out of the keypad bracket.

Step 4.5. Record the settings of jumpers J4 and J17 on the old Regulator board.

These jumpers are above of the terminal strip, as shown in figure 5.4.

Step 5.

Install the New Regulator Board in the Keypad Bracket

Step 5.1. Remove the new Regulator board from its anti-static wrapper. Make sure

the jumper settings on the new board match those on the old board.

Step 5.2. Slide the new Regulator board into the keypad bracket. Position the board

so that seven-segment displays appear in the display window in the
keypad.

Step 5.3. Connect the green-striped keypad ribbon cable to the new Regulator board.

Align the ribbon cable connector with the Regulator board connector and
carefully push the keyboard cable in until it snaps into place. Verify that it is
locked into position by gently tugging on the cable.

Figure 5.4 – Location of Jumpers J4 and J17 on the Regulator Board

34

-Pi

n R

ibb

on C

a

ble

J8

J4

J17

USER I/O TERMINAL STRIP

26-

P

in Ri

bbon Cabl

e

J5

J9

USER DISPLAY

J3

J7