PMI Regulator Operating Modes

3-1

C

HAPTER

3

PMI Regulator Operating Modes

The PMI Regulator’s default operating mode is idle. All other operating modes are
selected by the programmer in the Drive Control register (100/1100). Table 3.1 shows
the available operating modes. Note that the operating modes are mutually exclusive,
i.e., only one mode may be enabled at a time (this is checked by the interlock tests).

The PMI Regulator’s operating modes are shown in figure 3.1 and are described in the
following sections.

Table 3.1 – PMI Regulator Operating Modes

Operating

Mode

Drive Control

Register Bit

Mode Description

Idle

N/A

The PMI Regulator’s default operating mode during which no
algorithms are running.

Enable PMI Run

0

Executes the control algorithms.

Enable Tuning

1

Calculates gain values for the control algorithm.

Bridge Test
Enable

2

Performs a test to verify gate cable connections and power
devices.