PMI Regulator LED Summary

The following table summarizes the LEDs on the PMI Regulator. Refer to the SA3100
PMI Regulator instruction manual (S-3057) for more information on these LEDs.
Refer to the SA3100 Drive Configuration and Programming instruction manual
(S-3056) for more information regarding the UDC module’s dual port registers.

Name

Description

LED

OK

When lit, indicates the PMI Regulator passed its power-up
diagnostics and the on-board watchdog timer is being updated.

LED

COMM OK

When lit, indicates messages are being received correctly by the
PMI Regulator over the fiber-optic link.

LED

DRV RDY

When lit, indicates that the AC power technology hardware is
functioning properly.

Related Reg/Bit

202/1202 bit 11
FLT_PTM@

Power Technology Fault

LED

P.M. FLT

When lit, indicates one of the following fault conditions has been
detected by the PMI Regulator:

Related Reg/Bit

202/1202 bit 1
FLT_DCI@

DC Bus Overcurrent Fault

Related Reg/Bit

202/1202 bit 3
FLT_IOC@

Instantaneous Overcurrent Fault

Related Reg/Bit

202/1202 bit 6
FLT_CHG@

Charge Bus Time-out Fault

Related Reg/Bit

202/1202 bit 7
FLT_OT@

Over Temperature Fault

LED

EXT FLT

When lit, indicates one of the following fault conditions has been
detected by the PMI Regulator:

Related Reg/Bit

202/1202 bit 0
FLT_OV@

DC Bus Overvoltage Fault

Related Reg/Bit

202/1202 bit 2
FLT_GND@

Ground Current Fault

Related Reg/Bit

202/1202 bit 6
FLT_CHG@

Charge Bus Time-out Fault

Related Reg/Bit

202/1202 bit 10
FLT_OSP@

Over Speed Fault

Related Reg/Bit

101/1101 bit 2
EXT_LED@

Application Program Control