3-6

Diagnostics, Troubleshooting, and Start-Up Guidelines

Step 7. Test the bridge by measuring the voltage across the power devices. The

bridge test must be enabled and the appropriate value written to the Bridge
Test Code register (105/1105) as described below.

The value in the Bridge Test Code register specifies which power device
pairs to turn on. The value corresponds to a bit pattern, with the bits
described as follows:

• Bit 0: Phase U Upper Power Device

• Bit 1:Phase V Upper Power Device

• Bit 2:Phase W Upper Power Device

• Bit 3:Phase U Lower Power Device

• Bit 4:Phase V Lower Power Device

• Bit 5:Phase W Lower Power Device

a. Connect the voltmeter to the output terminals U, V, W for the power

devices being tested in accordance with table 3.2.

b. Turn on power to the drive.

c. Clear the Bridge Test Code register (105/1105, TST_CODE%).

Figure 3.3 – Power Device Test Locations

Left

Middle

Right

U

V

W

Upper

Lower

DC
Bus

+

Gate
Driver

Gate
Driver

Gate
Driver

Advertising