AutoMax Programming Executive Access Levels

H-1

A

PPENDIX

H

AutoMax Programming

Executive Access Levels

Rack Power Supply Keyswitch Position

Any

Position

PROTECT

SETUP

PROGRAM

User’s Access Level

Action

None

Any

Level

Data

Task

Rack

Data

Task

Rack

Force Common

No

No

No

No

No

Yes

Yes

Yes

Force Local

No

No

No

No

No

No

Yes

Yes

Force I/O

No

No

No

No

No

Yes

Yes

Yes

Set Common

No

No

No

No

No

Yes

Yes

Yes

Set Local

No

No

No

No

No

No

Yes

Yes

Set I/O

No

No

No

No

No

Yes

Yes

Yes

Set/Tune Tunable

No

No

No

Yes

Yes

No

Yes

Yes

Load Normal Config

No

No

No

No

No

No

No

Yes

Load Debug Config

No

No

No

No

No

No

No

Yes

Load Single POB File

No

No

No

No

No

No

Yes

1

1. Must have Task access to both tasks in the UDC

Yes

Load Single Task

No

No

No

No

No

No

2

2. A single task may be loaded with only Data access if the task does not already exist on the AutoMax Processor or UDC module.

Yes

Yes

Delete Task

No

No

No

No

No

No

Yes

Yes

Start Task

No

No

No

No

No

No

Yes

Yes

Stop Non-Critical Task

No

No

No

No

No

No

Yes

Yes

Save Task from Rack

No

Yes

3

3. Requires Task or Rack access.

No

Yes

Yes

No

Yes

Yes

Load All POB Files

No

No

No

No

No

Yes

Yes

Yes

Load All

No

No

No

No

No

No

No

Yes

Delete All Tasks

No

No

No

No

No

No

Yes

4

4. Must have Task access to all tasks.

Yes

Start All Tasks

No

No

No

No

No

No

Yes

4

Yes

Stop All Tasks

No

No

No

No

No

No

Yes

4

Yes

Load AutoMax OS

No

No

No

No

No

No

No

Yes

Load Single UDC OS

No

No

No

No

No

No

Yes

1

Yes

Load All UDC OS

No

No

No

No

No

No

Yes

1

Yes

Modify PC Task

No

No

No

No

No

No

Yes

Yes

Auto Run

No

No

No

No

No

Yes

Yes

Yes

Monitor

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Note that a user with privileged (Data, Task, or Rack) access may relinquish this privilege by timing out after two minutes off-line, or by
selecting to relinquish access on-line. Functions not listed in the table do not require privileged access.