PMI Regulator Operating Modes

3-3

Figure 3.2 – Internal DC Bus Control Flowchart

Idle

Wait for Bus to

Charge

Nominal Bus

Voltage

Reached?

Open Pre-Charge

Contactor

Auxiliary

Contacts

Closed?

PMI Sets

BUS_RDY@

Bus Charged

PMI Closes
Pre-Charge

Contactor

More than 10

Seconds

Elapsed?

Fault Occurs

Register 202/1202

More than 10

Seconds

Elapsed?

Open Pre-Charge

Contactor

Fault

Occurs?

No

Wait for AC Line

AC Line Status

From Power Module

= TRUE

More than 10

Seconds

Elapsed?

Yes

No

Common

Bus or Hi HP

Stand-Alone

?

Yes

Hi HP

Stand-Alone

?

BUS_ENA@ On*

Begin 10 Second
Timer

**

**

**

**

**

**

*BUS_ENA@ must transistion from off to on to start the bus

charging process.

**BUS_ENA@ must remain on during the drive operation

No

Hi HP

?

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No