4-12

Diagnostics, Troubleshooting, and Start-Up Guidelines

Step 1. Test each digital input by initiating the input and verifying that the appropriate

bit (displayed on the screen) goes on.

Step 2. Test each digital output by forcing the bit on and verifying that the signal is

present on the terminal points.

Step 3. Test any analog current or voltage output channel being used by writing a

value shown in table 4.3 to the channel and verifying with an ammeter or
voltmeter that the signal on the terminal points (4-20mA, 0-20mA, +/- 10V, or
0-10V) is proportional.

Step 4. Test any analog current or voltage input channel being used by verifying that

the input signal in that channel (4-20mA, 0-20mA, +/- 10V, or 0-10V) is
proportional to the value displayed in appropriate register.

Digital Data Formats

Some digital I/O modules are only 8 bits and do not require the full 16 bits of the
assigned UDC register. If the module is only 8 bits, then bits 8 through 15 are not
used. Bit 0 is defined as Digital I/O channel 0, bit 1 is channel 1, etc.

Flex I/O module IB10X0B6 (10 input/6 output digital combo module) is mapped to
UDC memory as shown below, with the lower ten bits configured as inputs and the
upper 6 bits as outputs.

0 = Output

I = Input

Data Format: 8-bit Digital I/O

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Data

-

-

-

-

-

-

-

-

I/O I/O I/O I/O I/O I/O I/O I/O

Data Format: Module IB10X0B6 - 10 Input / 6 Output Digital Combo

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Data

O

O

O

O

O

O

I

I

I

I

I

I

I

I

I

I

Advertising