Rockwell Automation SA3100 Diag,Troublesht,Startup,Guide User Manual

Page 53

Advertising
background image

Drive Fault Register

A-3

Over Temperature Fault

Bit 7

The Over Temperature Fault bit is set if the
thermistor in the Power Module detects a
temperature of 100° C or more.

Hex Value:

0080H

Sug. Var. Name:

FLT_OT@

Access:

Read only

UDC Error Code:

1016

LED:

P.M. FLT

Resolver Broken Wire Fault

Bit 8

The Resolver Broken Wire Fault bit is set if a
sine or cosine signal from the resolver is
missing due to a broken wire or if the
resolver gain tunable (RES_GAN%) has
been set too low.

Hex Value:

0100H

Sug. Var. Name:

FLT_TBW@

Access:

Read only

UDC Error Code:

1008

LED:

FDBK OK

Resolver Fault

Bit 9

The Resolver Fault bit is set if the fuse
blows on the Resolver & Drive I/O board.
This indicates the board has failed and must
be replaced.

Hex Value:

0200H

Sug. Var. Name:

FLT_RES@

Access:

Read only

UDC Error Code:

1009

LED:

N/A

Overspeed Fault

Bit 10

The Over Speed Fault bit is set if the motor’s
velocity exceeds the value entered as the
Over Speed Trip (RPM) configuration
parameter.

Hex Value:

0400H

Sug. Var. Name:

FLT_OSP@

Access:

Read only

UDC Error Code:

1010

LED:

EXT FLT

Power Technology Fault

Bit 11

The Power Technology Fault bit is set to
indicate a problem with the AC power
technology circuit on the PMI Regulator
motherboard.

Hex Value:

0800H

Sug. Var. Name:

FLT_PTM@

Access:

Read only

UDC Error Code:

1011

LED:

OK

Register 222/1222 provides additional diagnostics if this fault occurs.

PMI Regulator Bus Fault

Bit 13

The PMI Regulator Bus Fault bit is set if the
Resolver & Drive I/O board or the AC power
technology circuit does not respond to
requests from the PMI Processor. This
indicates a hardware problem in the PMI
Regulator.

Hex Value:

2000H

Sug. Var. Name:

FLT_BUS@

Access:

Read only

UDC Error Code:

1013

LED:

N/A