Rockwell Automation SA3100 Diag,Troublesht,Startup,Guide User Manual

Page 70

Advertising
background image

F-2

Diagnositics, Troubleshooting, and Start-Up Guidelines

LED

I/O FLT

When lit, indicates communication between a Flex I/O module and
the PMI Regulator has been disrupted, or that Flex I/O is configured
but is not plugged in.

Related Reg/Bit

203/1203 bit 13
WRN_I/O@

Flex I/O Communication Error

LED

FDBK OK

When lit, indicates that the Resolver & Drive I/O board is receiving
feedback from the resolver and that no resolver feedback faults have
been detected.

Related Reg/Bit

202/1202 bit 8
FLT_TBW@

Resolver Feedback Broken Wire

LED

RPI

When lit, indicates the run permissive input signal has been
detected.

Related Reg/Bit

201/1201 bit 0
RPI@

RPI Input Status

LED

MCR

When lit, indicates that the MCR output signal is being driven on.

LED

AUX IN1

When lit, indicates the presence of a 115V signal on this input.

Related Reg/Bit

201/1201 bit 1
M_FDBK@

Aux Input 1/MFDBK Status

LED

AUX IN2

When lit, indicates the presence of a 115V signal on this input.

Related Reg/Bit

201/1201 bit 2
AUX_IN2@

Aux Input 2 Status

LED

AUX IN3

When lit, indicates the presence of a 115V signal on this input.

Related Reg/Bit

201/1201 bit 3
AUX_IN3@

Aux Input 3 Status

LED

AUX IN4

When lit, indicates the presence of a 115V signal on this input.

Related Reg/Bit

201/1201 bit 4
AUX_IN4@

Aux Input 4 Status

LED

AUX IN5

When lit, indicates the presence of a 115V signal on this input.

Related Reg/Bit

201/1201 bit 5
AUX_IN5@

Aux Input 5 Status

LED

AUX OUT

When lit, indicates the output signal has been turned on.

Related Reg/Bit

101/1101 bit 4
AUX_OUT@

Aux Output Status

Name

Description

Advertising