A-2

Diagnositics, Troubleshooting, and Start-Up Guidelines

Ground Current Fault

Bit 2

The Ground Current Fault bit is set if ground
current exceeds the hardware trip point.

Hex Value:

0004H

Sug. Var. Name:

FLT_GND@

Access:

Read only

UDC Error Code:

1021

LED:

EXT FLT

For models A001/Q001 and A003/Q003 the hardware trip point is 20A @ 10V. For
all other models it is 100A @ 10V.

Instantaneous Overcurrent Fault

Bit 3

The Instantaneous Overcurrent (IOC) Fault
bit is set if either of the following conditions
is detected:

Hex Value:

0008H

Sug. Var. Name:

FLT_IOC@

Access:

Read only

UDC Error Code:

1017

LED:

P.M. FLT

Output current is greater than 200% of the peak RMS current. Bits 0 to 5 in
register 204/1204 indicate which power device detected the overcurrent.

An inverter power device fault is detected. Bit 6 in register 204/1204 will be set if
the IOC fault is due to a power device overcurrent.

Power Supply Fault

Bit 4

The Power Supply Fault bit is set if the
output of the isolated +12V supply, or the
output of the external power supply for a G
or H frame drive, falls below the configured
low voltage threshold.

Hex Value:

0010H

Sug. Var. Name:

FLT_12V@

Access:

Read only

UDC Error Code:

1022

LED:

P.M. FLT

Register 222/1222 provides additional diagnostics if this fault occurs.

Charge Bus Time-Out Fault

Bit 6

The Charge Bus Time-out Fault bit is set to
indicate any of the conditions listed below.
Register 222/1222 provides additional
diagnostics if this fault occurs.

Hex Value:

0040H

Sug. Var. Name:

FLT_CHG@

Access:

Read only

UDC Error Code:

1024

LED:

EXT FLT and

P.M. FLT

The DC bus is not fully charged within 10 seconds after the bus enable bit
(register 100/1100, bit 4) is set.

The drive is on and feedback indicates that the pre-charge contactor has opened.

DC bus voltage is less than the value stored in the Power Los Fault Threshold
(PLT_E0%) tunable variable.

If the Charge Bus Time-Out Fault bit is set, verify that incoming power is at the
appropriate level. If the power level is correct, the problem is in the Power Module.