Table 4.3 – analog data format -13 – Rockwell Automation SA3100 Diag,Troublesht,Startup,Guide User Manual

Page 45

Advertising
background image

Installation and Start-Up Guidelines

4-13

Analog Data Formats

Data is returned from the Flex I/O module’s analog-to-digital converter with 12-bit
resolution. The value is left-justified into a 16-bit field, reserving the most significant bit
for a sign bit.

A/D Unipolar Data

11 10 09 08 07 06 05 04 03 02 01 00

⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓

Analog Value

0*

14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Input

* = Always positive

A/D Bipolar Data

S

10 09 08 07 06 05 04 03 02 01 00

⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓

Analog Value

S

14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

D/A Data

S

11 10 09 08 07 06 05 04 03 02 01 00

Output

⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓

Analog Value

S

14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Table 4.3 – Analog Data Format

1

1. The value returned from the A/D converter is 12-bits long, left-justified in a 16-bit field. The most significant bit is reserved for a sign bit.

Current

(mA)

4-20 mA

Mode

0-20 mA

Mode

Voltage (V)

+/- 10 Volt Mode

0-10 Volt

Mode

Input

Output

-10.5

-32768

-32768

0

0

-10.0

-31200

-31208

1

1560

-9.0

-28080

-28088

2

3120

-8.0

-24960

-24968

3

4680

-7.0

-21840

-21848

4

0

6240

-6.0

-18720

-18728

5

1927

7800

-5.0

-15600

-15608

6

3854

9360

-4.0

-12480

-12488

7

5782

10920

-3.0

-9360

-9368

8

7710

12480

-2.0

-6240

-6248

9

9637

14040

-1.0

-3120

-3128

10

11565

15600

0

0

0

0

11

13492

17160

1.0

3120

3120

3120

12

15420

18720

2.0

6240

6240

6240

13

17347

20280

3.0

9360

9360

9360

14

19275

21840

4.0

12480

12480

12480

15

21202

23400

5.0

15600

15600

15600

16

23130

24960

6.0

18720

18728

18728

17

25057

26520

7.0

21840

21848

21848

18

26985

28080

8.0

24960

24968

24968

19

28912

29640

9.0

28080

28088

28088

20

30840

31200

10.0

31200

31208

31208

21

32767

32760

10.5

32752

32760

32760