3 testing feedback registers and bits, 3 testing feedback registers and bits -14, Table 4.4 – feedback registers and bits -14 – Rockwell Automation SA3100 Diag,Troublesht,Startup,Guide User Manual

Page 46

Advertising
background image

4-14

Diagnostics, Troubleshooting, and Start-Up Guidelines

4.7.8.3 Testing Feedback Registers and Bits

This section describes how to test the feedback registers and bits listed in table 4.4.
Fault, warning, and interlock registers are described in Appendices A, B, and C. Use
the AutoMax Programming Executive I/O Monitor function to display the registers and
bits in the format listed in table 4.4.

Step 1. Verify that register 200/1200, bit 15 is on. This bit is on when PMI operating

system has been successfully downloaded from the UDC module to the PMI
Regulator.

Step 2. Check each of the inputs identified by bits 1 through 5 of register 201/1201

by applying 115V to the appropriate pins on the Drive I/O connector on the
Resolver and Drive I/O board and verifying that the appropriate bit is on.
Refer to instruction manual S-3057, PMI Regulator, for the pinout
description.

Table 4.4 – Feedback Registers and Bits

Drive A/B

Variable Name

Description

200 / 1200

Bit 15

(PMI_OK@)

Drive Status Register
PMI Operating System Loaded

201 / 1201

I/O Status Register

Bit 0

(RPI@)

Run Permissive Input

Bit 1

(M_FDBK@)

M-Contactor Feedback Input or

(AUX_IN1@)

115VAC Auxiliary Input 1

Bit 2

(AUX_IN2@)

115VAC Auxiliary Input 2

Bit 3

(AUX_IN3@)

115VAC Auxiliary Input 3

Bit 4

(AUX_IN4@)

115VAC Auxiliary Input 4

Bit 5

(AUX_IN5@)

115VAC Auxiliary Input 5

Bit 8

(STR_DET@)

External Strobe Detected

203 / 1203

Drive Warning Register

Bit 13

(WRN_I/O@)

Flex I/O Communication Error

206 / 1206

(BUS_VDC%)

DC Bus Voltage Feedback (1=1V)

207 / 1207

(BUS_IDC%)

DC Bus Current Feedback (10=1A)

208 / 1208

(GI_FB%)

Ground Current Feedback (10=1A)

209 / 1209

(V_FB%)

Voltage Feedback (1=1V RMS)

210 / 1210

(I_FB%)

Current Feedback (10=1A RMS)

211 / 1211

(I_FBN%)

Current Feedback (normalized)

212 / 1212

(ID_FBN%)

Id Feedback (normalized)

213 / 1213

(IQ_FBN%)

Iq Feedback (normalized)

214 / 1214

(ANA_IN%)

User Analog Input (-2048 =-10V to +2047 = +10V)

215 / 1215

(RES_SCN_POS%)

Resolver Scan Position (-32768 to 32767)

216 / 1216

(RES_STR_POS%)

Resolver Strobe Position (-32768 to 32767)

217 / 1217

(RPM%)

Revolutions Per Minute

218 / 1218

(SLIP_FB%)

Slip Feedback (100 = 1 Hz)

219 / 1219

(SEL_VAR%)

Selected Variable

222 / 1222

(DIAG_FLT%)

Diagnostic Fault Code