Diagnositics, Troubleshooting, and Start-Up Guidelines

UDC Run Fault

Bit 14

The UDC Run Fault bit is set if the UDC task
stops while the minor loop is running in the
PMI Regulator.

Hex Value:

4000H

Sug. Var. Name:

FLT_RUN@

Access:

Read only

UDC Error Code:

1014

LED:

N/A

Communication Lost Fault

Bit 15

The Communication Lost Fault bit is set if
the fiber-optic communication between the
PMI processor and the UDC module is lost
due to two consecutive errors of any type.

Hex Value:

8000H

Sug. Var. Name:

FLT_COM@

Access:

Read only

UDC Error Code:

1015

LED:

N/A

This bit is set only after communication between the PMI Regulator and UDC
module has been established. This bit should be used in the run permissive logic for
the drive. Also refer to the description of the CCLK Synchronized bit (register
200/1200, bit 14) in S-3056.

The following table shows how the operation of the digital I/O and Flex I/O is
affected when one or both of the fiber-optic cables is disconnected:

Table A.1 – Effect of a Disconnected Fiber-Optic Cable

Resolver & Drive I/O

Analog & Digital

Cable Disconnected

MCR AUX OUT

Digital Inputs

Flex Inputs

Flex Outputs

UDC XMT/PMI RCV

Turn Off

1

Update

Last Value

2

Held Reset

3

PMI XMT/UDC RCV

Turn Off

1

Last Value

2

Last Value

2

UDC Control

1. Outputs will remain off until the Fault Reset bit (register 100/1100, bit 8, FLT_RST@) is turned on. At that time, they will be under the

control of the application tasks.

2. The application task(s) in the AutoMax rack must monitor the CCLK Synchronized bit (register 200/1200, bit 14, CCLK_OK@) to

determine if the digital input data is valid.

3. As soon as communication is re-established, outputs become active again; the Warning Reset bit (register 100/1100, bit 9,

WRN_RST@) does not need to be set.