Status of Data in the AutoMax Rack After a STOP_ALL Command or STOP_ALL Fault

G-1

A

PPENDIX

G

Status of Data in the AutoMax

Rack After a STOP_ALL

Command or STOP_ALL Fault

AutoMax

Processor

UDC Module

PMI

Processor

LOCAL tunable variables

retained

retained

retained

LOCAL variables

retained

reset to 0

N/A

COMMON memory variables

non-volatile are
retained; others are
reset to 0

N/A

N/A

I/O variables
(including UDC dual port memory)

inputs retained and
updated;
outputs are reset to 0

inputs retained and
updated;
outputs are reset to 0

all I/O is reset to 0

Input values, including:

Feedback registers
UDC/PMI communication
status registers
UDC Error Log info

retained

retained

N/A

Output values, including:

Command registers
Application registers
ISCR registers
Scan-per-interrupt register
Scans-per-interrupt counter

reset to 0

reset to 0

N/A

Parameter configuration variables

N/A

retained

N/A

UDC test switch information

N/A

retained

N/A

D/A setup configuration

N/A

retained

N/A

Operating system

retained

retained

retained