Rockwell Automation SA3100 Diag,Troublesht,Startup,Guide User Manual
Page 64

D-2
Diagnositics, Troubleshooting, and Start-Up Guidelines
AC Power Technology Calibration and Power-Up Faults:
The following calibration and power-up diagnostic faults indicate an irreparable hardware failure of the AC
power technology circuitry on the PMI Regulator motherboard. If any of these faults occurs, replace the PMI
Regulator motherboard.
Register 202, bit 11 (FLT_PTM@) will be set.
Code
Fault
Action
1
D/A high voltage error (+3.3V 10% out of tolerance)
Replace PMI Regulator
Motherboard
2
D/A low voltage error (-3.3V 10% out of tolerance)
3
Torque current loop proportional gain not within calibration limits
(14<g<30)
4
Flux current loop proportional gain not within calibration limits
(14<g<30)
5
Flux current loop integrator time constant not within calibrated
limits
6
Torque current loop integrator time constant not within
calibrated limits
7
Modulation index error
8
Harmonic DAC limit error
9
Modulation range error
10
Harmonic DAC range error
11
Programmable current limit or the ground fault limit fault
12
Voltage feedback integrator error
13
A/D converter interrupt error
14
Pulse Width Modulator frequency error
15
DC bus current not zero at power-up.
16
Phase U current not zero at power-up.
17
Phase W current not zero at power-up.