Environmental

Temperature Ranges (for altitude less than 950 m
or 3117 ft)

10 °C to 35 °C (50 °F to 95 °F) with no direct
sunlight on the equipment.

Humidity Percentage Range

10% to 80% Relative Humidity with 26 °C (78.8
°F) maximum dew point.

Relative Humidity

Storage

5% to 95% RH with 33 °C (91 °F) maximum dew
point. Atmosphere must be non-condensing at
all times.

Maximum Vibration

Operating

0.26 G

rms

at 5 Hz to 350 Hz (all operation

orientations).

Storage

1.87 G

rms

at 10 Hz to 500 Hz for 15 min (all six

sides tested).

Maximum Shock

Operating

One shock pulse in the positive z axis of 31 G
for 2.6 ms in all operational orientations.

Storage

Six consecutively executed shock pulses in the
positive and negative x, y, and z axes (one pulse
on each side of the system) of 71 G for up to 2
ms.

Maximum Altitude

Operating

3048 m (10,000 ft).

Storage

12,000 m (39,370 ft).

Operating Altitude De-rating

Up to 35 °C (95 °F)

Maximum temperature is reduced by 1 °C/300
m (1 °F/547 ft) above 950 m (3,117 ft).

35 °C to 40 °C (95 °F to 104 °F)

Maximum temperature is reduced by 1 °C/175
m (1 °F/319 ft) above 950 m (3,117 ft).

40 °C to 45 °C (104 °F to 113 °F)

Maximum temperature is reduced by 1 °C/125
m (1 °F/228 ft) above 950 m (3,117 ft).

Particulate Contamination

NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from
particulates and gaseous contamination. If it is determined that levels of particulates or gaseous
pollution are beyond the limits specified below and are the reason for the damage and/or failures
to your equipment, it may be necessary for you to re-mediate the environmental conditions that
are causing the damage and/or failures. Re-mediation of environmental conditions will be the
responsibility of the customer.

104