Dell PowerVault DR6000 User Manual

Page 117

Advertising
background image

Error Code

Message Information

3.

If the issue persists, see

Getting Help

.

PSU0035

Message

An over voltage fault detected on power supply <number>.

Action

Check input power or reinstall the power supply. If the issue
persists, see

Getting Help

.

PSU0036

Message

An over current fault detected on power supply <number>.

Details

This failure may be the result of an electrical issue with
cables or subsystem components in the system.

Action

1.

Remove and reinstall the power supply.

2.

Check cables and subsystem components in the system

for damage.

3.

If the issue persists, see

Getting Help

.

PSU0037

Message

Fan failure detected on power supply <number>.

Action

Check for fan blockage. If the problem persists, see

Getting

Help

.

PSU0076

Message

A power supply wattage mismatch is detected; power supply
<number> is rated for <value> watts.

Details

Power supplies should be of the same input type and power
rating.

Action

Install matched power supplies and review this manual for
proper configuration.

PSU1201

Message

Power supply redundancy is lost.

Details

The power supply tries to operate in a degraded state.
System Performance and power redundancy may be
degraded or lost.

Action

Check input power. Reinstall the power supply. If the issue
persists, see

Getting Help

.

PSU1204

Message

The power supplies are not redundant. Insufficient resources
to maintain normal operations.

Details

The current power operational mode is non-redundant
because of a power supply exception, a power supply
inventory change, or a system power inventory change.

117

Advertising