Environmental

Air Filtration

NOTE: Applies to data center environments
only. Air filtration requirements do not apply
to IT equipment designed to be used outside
a data center, in environments such as an
office or factory floor.

Data center air filtration as defined by ISO Class
8 per ISO 14644-1 with a 95% upper confidence
limit.

NOTE: Air entering the data center must
have MERV11 or MERV13 filtration.

Conductive Dust

NOTE: Applies to data center and non-data
center environments.

Air must be free of conductive dust, zinc
whiskers, or other conductive particles.

Corrosive Dust

NOTE: Applies to data center and non-data
center environments.

• Air must be free of corrosive dust.
• Residual dust present in the air must have a

deliquescent point less than 60% relative

humidity.

Gaseous Contamination

NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.

Copper Coupon Corrosion Rate

<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.

Silver Coupon Corrosion Rate

<200 Å/month as defined by AHSRAE TC9.9.

105