Error Code

Message Information

SEL0008

Message

Log is full.

Details

When the event log is full, additional events are not written
to the log. Older events may be overwritten and lost. This
message may also appear if the user disabled event logging.

Action

Backup and clear log.

SEL0012

Message

Could not create or initialize the system event log.

Details

If the system event log fails to initialize, platform status and
failure events are not captured. Some management software
do not report platform exceptions.

Action

Reboot the management controller or iDRAC. Cycle system
input power. If problem persists call support.

SEL1204

Message

An unknown system hardware failure detected.

Details

If the system event log failed to initialize, platform status and
failure events are not captured. Some management software
do not report platform exceptions.

Action

Re-configure system to the minimum supported
configuration. If issues persists, contact support.

TMP0118

Message

The system inlet temperature is less than the lower warning
threshold.

Details

Ambient air temperature is too cool.

Action

Check the system operating environment.

TMP0119

Message

The system inlet temperature is less than the lower critical
threshold.

Details

Ambient air temperature is too cool.

Action

Check the system operating environment.

TMP0120

Message

The system inlet temperature is greater than the upper
warning threshold.

Details

Ambient air temperature is too warm or one or more fans
may have failed.

Action

Check the system operating environment and review event
log for fan failures.

120