KEYENCE DL-DN1 User Manual

Page 15

Advertising
background image

1-3 Names and Functions of Each Part

1-5

- DeviceNet Compatible Network Unit DL-DN1 User's Manual -

1

B

e

for

e Us

in

g

Item

Description

(2) Operating mode set-

ting switch

Sets the operating mode of the DL-DN1 in the DeviceNet.
The data that can be handled in remote I/O communica-
tion varies with each operating mode.

Basic mode
Use switch bits 1 and 2 to configure the basic mode.

Default value: 3-output mode

• The contents of output and current value vary depend-

ing on the sensor amplifiers to be connected.
Examples: 3-level judgment output for 3-output mode;
5-level judgment output for 5-output mode. Current
value: comparator value.

• The size of occupied memory depends on the number

of amplifiers to be connected.

Extended mode
Switch bits 3 and 4 can be set to add one of the following
extended functions to the basic mode.

Default value: No extended mode
The size of occupied memory depends on the number of
amplifiers to be connected.

Switch setting

Operating mode

Occupied memory

IN area

OUT area

3-output mode

8 byte

0 byte

5-output mode

12 byte

0 byte

"3-output + current value"
mode

14 to 70 byte

0 byte

"5-output + current value"
mode

18 to 74 byte

0 byte

Switch setting

Operating mode

Occupied memory

IN area

OUT area

No extended mode

-

-

External input mode 14 to 84 byte

6 to 10 byte

"External input +

BANK change"

mode

18 to 88 byte 10 to 14 byte

"External input +

setting value change" mode

22 to 96 byte 24 to 40 byte