2-2 Wiring

2-9

- DeviceNet Compatible Network Unit DL-DN1 User's Manual -

2

Con

nect

io

n a

nd

Co
nf

igu
rat

ion

„Connecting the cable

Use the following procedures to wire to the DeviceNet connector supplied with the DL-
DN1.

1

Connect the trimmed cable to the DeviceNet connector.

Insert the cable completely.

2

Attach the DeviceNet connector to the DL-DN1.

Plug the connector into the DL-DN1 and secure it down with the screws on each
end. (Tightening torque: 0.2 to 0.3 N•m)

Wire color

Signal name

Function

Black

V -

Connects 0 VDC of the communication power supply.

Blue

CAN_L

Communication signal (Low)

Bare wire

SHIELD

Connects the shield of the DeviceNet cable.

White

CAN_H

Communication signal (High)

Red

V +

Connects 24 VDC of the communication power supply.