5-3 Troubleshooting

5-6

- DeviceNet Compatible Network Unit DL-DN1 User's Manual -

5

Ap
pend

ix

„Network status indicator (NS)

This lamp indicates whether the DL-DN1 is properly communicating with the
DeviceNet.

LED status

Condition

Corrective action

Green

Solid

Communicating properly.

-

Flashing

The DL-DN1 is connected
to the network, but the com-
munication with the master
unit is not established.

Check that the DL-DN1 is regis-
tered in the master unit.

The DeviceNet cable was
disconnected while in oper-
ation.

Check that the DeviceNet cable
is connected correctly.

Red

Solid

Network error.

Check that the node address of
the DL-DN1 is not duplicated
with that of another slave unit.

Flashing

Minor network error.

Check that the data link is prop-
erly configured, and then cycle
power.

Green/
red

Flashing

The DL-DN1 is checking its
operation in the power-on
process.

After completing the check, the
DL-DN1 automatically switches
to the normal state.

Not lit

Not connected to the net-
work.

Check that the DL-DN1 is cor-
rectly connected with the sensor
amplifiers.

Advertising