2 device maps, Co mm u ni c a ting w ith t he fd -m h s er ie s – KEYENCE DL-CL1 User Manual

Page 39

Advertising
background image

3-2 Device Maps

3-11

3

Co
mm

u

ni

c

a

ting
w

ith t
he FD

-M

H

s

er

ie

s

- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-MH) -

Operating

mode

Device no.

(HEX)

Name

Communication

method

Description

Reading range

Monitor mode

2

Full mode

1

Full mode

2

RX[n] + 40
to 49

(Not used)

-

-

-

RX[n] + 4F

System
reserved

-

Unusable

RX[n] + 50 Sensor ready

*2

Used when communicating under handshake
control program.
This is output when command execution is
ready.

0: In preparation
1: Ready

RX[n] + 51

Command
complete

*2

Used when communicating under handshake
control program.
This is output when command execution is
complete.

0->1: Execution
complete

RX[n] + 52 Command error

*2

Used when communicating under handshake
control program.
This is output when an error occurs during
command execution.

0:No Error
1:Error

RX[n] + 53

Current Value
Update Locked

-

This is output when current value update is
locked (current value update lock request
(RY[n] + 53) is enabled).

0: Update
enabled
1: Update locked

RX[n] + 54
to 5D

System
reserved

-

Unusable

RX[n] + 60
to 69

(Not used)

-

-

-

RX[n] + 6F (Not used)

-

-

-

RY[n] + 70
to 79

Instantaneous
fl ow rate
setting-1 (P1)
rewrite complete
ID 01 to ID 10

*3

Used when rewriting a setting value.
This is output when the instantaneous fl ow
rate setting value 1 (P1) has been rewritten.
The output of each sensor amplifi er (ID 01 to
ID 10) corresponds to each RX.

0->1: Rewrite
complete

RX[n] + 7F

Instantaneous
fl ow rate
setting-1 (P1)
rewrite error

*3

Used when rewriting a setting value.
This is output if an error occurs with a sensor
amplifi er of any ID number during rewriting of
instantaneous fl ow rate setting value 1 (P1).

0:No Error
1:Error

RX[n] + 80
to 89

Instantaneous
fl ow rate
setting-2 (P2)
rewrite complete
ID 01 to ID 10

*3

Used when rewriting a setting value.
This is output when the instantaneous fl ow
rate setting value 2 (P2) has been rewritten.
The output of each sensor amplifi er (ID 01 to
ID 10) corresponds to each RX.

0->1: Rewrite
complete

RX[n] + 8F

Instantaneous
fl ow rate
setting-2 (P2)
rewrite error

*3

Used when rewriting a setting value.
This is output if an error occurs with a sensor
amplifi er of any ID number during rewriting of
instantaneous fl ow rate setting value 2 (P2).

0:No Error
1:Error

RX[n] + 90
to 99

Temperature
upper limit
setting rewrite
complete ID 01
to ID 10

*3

Used when rewriting a setting value.This
is output when the temperature upper limit
setting value has been rewritten. The output
of each sensor amplifi er (ID 01 to ID 10)
corresponds to each RX.

0->1: Rewrite
complete

RX[n] + 9F

Temperature
upper limit
rewrite error

*3

Used when rewriting a setting value.
This is output if an error occurs with a sensor
amplifi er of any ID number during rewriting of
temperature upper limit setting value.

0:No Error
1:Error

RX[n] + A0
to A9

Temperature
lower limit
setting rewrite
complete ID 01
to ID 10

*3

Used when rewriting a setting value.
This is output when the temperature lower
limit setting value has been rewritten. The
output of each sensor amplifi er (ID 01 to ID
10) corresponds to each RX.

0->1: Rewrite
complete