2 device maps, Co mm u ni c a ting w ith t he fd -m h s er ie s, Remote output ry (master station -> dl-cl1) – KEYENCE DL-CL1 User Manual

Page 40

Advertising
background image

3-2 Device Maps

3-12

- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-MH) -

Co
mm

u

ni

c

a

ting
w

ith t
he FD

-M

H

s

er

ie

s

3

Number [n] denotes the first relay number assigned to the DL-CL1.

*1

See

"Reading an Output from a Sensor Amplifier" (page 3-17).

*2

See

"Reading/Writing Settings or Status of a Sensor Amplifier" (page 3-21).

See

"Issuing a Motion Command to a Sensor Amplifier" (page 3-20).

*3

See

"Rewriting a Setting Value of a Sensor Amplifier" (page 3-21).

Remote Output RY (Master Station -> DL-CL1)

Operating

mode

Device no.

(HEX)

Name

Communication

method

Description

Reading

range

Monitor mode

2

Full mode

1

Full mode

2

RX[n] + AF

Temperature
lower limit rewrite
error

*3

Used when rewriting a setting value.
This is output if an error occurs with a sensor
amplifi er of any ID number during rewriting of
temperature lower limit setting value.

0:No Error
1:Error

RX[n] + B0
to B9

Integrated fl ow
quantity setting-1
rewrite complete
ID 01 to ID 10

*3

Used when rewriting a setting value.
This is output when the integrated fl ow
quantity setting value 1 has been rewritten.
The output of each sensor amplifi er (ID 01 to
ID 10) corresponds to each RX.

0->1: Rewrite
complete

RX[n] + BF

Integrated fl ow
quantity setting-1
rewrite error

*3

Used when rewriting a setting value.
This is output if an error occurs with a sensor
amplifi er of any ID number during rewriting of
integrated fl ow quantity setting value 1.

0:No Error
1:Error

RX[n] + C0
to EF

System reserved

-

Unusable

RX[n] + 7B

Remote ready

-

This is output when the DL-CL1 is correctly
connected to the CC-Link system.
1: Proper communication is provided.Data
from the sensor amplifi er will be updated.
0: Proper communication is not provided.Data
from the sensor amplifi er will not be updated.

0: In
preparation
1: Ready

RX[n] + DB

RX[n] + 17B

Operating

mode

Device no.

(HEX)

Name

Communication

method

Description

Writing range

Monitor mode

2

Full mode

1

Full mode

2

RY[n] + 00
to 09

Integration reset
input ID 01 to ID 10

*1

Receives integration reset input by assigning
each sensor amplifi er (ID 01 to ID 10) to
each RY.

0: OFF
1: ON

RY[n] + 0F System reserved

-

Unusable

RY[n] + 10
to 19

Flow rate hold reset
input ID 01 to ID 10

*1

Receives fl ow rate hold reset input by
assigning each sensor amplifi er (ID 01 to ID
10) to each RY.

0: OFF
1: ON

RY[n] + 1F System reserved

-

Unusable

RY[n] + 20
to 29

(Not used)

-

-

-

RY[n] + 2F System reserved

-

Unusable

RY[n] + 30
to 39

Temperature hold
reset input ID 01 to
ID 10

*1

Receives temperature hold reset input by
assigning each sensor amplifi er (ID 01 to ID
10) to each RY.

0: OFF
1: ON

RY[n] + 3F

System reserved

-

Unusable

RY[n] + 40
to 49

(Not used)

-

-

-

RY[n] + 4F
to 50

System reserved

-

Unusable

RY[n] + 51

Request for
command

*2

Used when communicating under handshake
control program.
This is input when requesting command
execution.

0->1: Request
execution

RY[n] + 52 System reserved

-

Unusable

Advertising