4 command parameter list, Co mm u ni c a ting w ith t he fd -m h s er ie s – KEYENCE DL-CL1 User Manual

Page 56

Advertising
background image

3-4 Command Parameter List

3-28

- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-MH) -

Co
mm

u

ni

c

a

ting
w

ith t
he FD

-M

H

s

er

ie

s

3

00

nn40

Group-2 entry
count

R

-

8

nn41

Instantaneous
flow rate setting 1
(P1)

*7

R/W

FD-MH10A

03.00

00.00 to 30.00

FD-MH50A

015.0

000.0 to 100.0

FD-MH100A

030.0

000.0 to 200.0

FD-MH500A

100.0

000.0 to 999.9

nn42

Instantaneous
flow rate setting 2
(P2)

*7

R/W

FD-MH10A

10.0

00.00 to 30.00

FD-MH50A

050.0

000.0 to 100.0

FD-MH100A

100.0

000.0 to 200.0

FD-MH500A

200.0

000.0 to 999.9

nn43

Temperature
upper limit setting

*8

R/W

-

080.0

100.0: Disable upper limit detection
0.001 to 099.9: Upper limit value

nn44

Temperature
lower limit setting

*9

R/W

-

005.0

000.0: Disable lower limit detection
0.001 to 099.9: Lower limit value

nn45

Integrated flow
quantity setting 1

R/W

-

0150

0000 to 9999

nn46

Integrated flow
quantity setting 2

R/W

-

9999

0000 to 9999

nn47

Instantaneous
flow rate setting 3
(P3)

*7

R/W

FD-MH10A

13.00

00.00 to 30.00

FD-MH50A

065.0

000.0 to 100.0

FD-MH100A

130.0

000.0 to 200.0

FD-MH500A

400.0

000.0 to 999.9

nn48

Instantaneous
flow rate setting 4
(P4)

*7

R/W

FD-MH10A

20.00

00.00 to 30.00

FD-MH50A

100.0

000.0 to 100.0

FD-MH100A

200.0

000.0 to 200.0

FD-MH500A

500.0

000.0 to 999.9

nn49 to

nn5F

System reserved

nn60

Group-3 entry
count

R

-

5

nn61

Key lock function

R/W

-

0

0: Deactivate key lock
1: Key lock

nn62

System reserved

nn63

Analog output
selection

*10

R/W

-

0

0: Standard
1: Free range analog

nn64

Free range analog
upper limit

*10

R/W

FD-MH10A

10.0

0.0 ~ 30.00 (Settable unit: 0.1)

FD-MH50A

050

000 to 100 (Settable unit: 5)

FD-MH100A

100

000 to 200 (Settable unit: 10)

FD-MH500A

0500

0000 to 1000 (Settable unit: 50)

nn65

Free range analog
lower limit

*10

R/W

FD-MH10A

0.0

0.0 ~ 30.00 (Settable unit: 0.1)

FD-MH50A

000

000 to 100 (Settable unit: 5)

FD-MH100A

000

000 to 200 (Settable unit: 10)

FD-MH500A

0000

0000 to 1000 (Settable unit: 50)

nn66 to

nn7F

System reserved

nn80

Group-4 entry
count

R

-

29

nn81

System reserved

nn82

Detection mode

R/W

-

0

0: F-1
1: F-2
2: F-3
3: A-1
4: A-2

Data

category

(HEX)

Data

number

(HEX)

Name

Description

Attribute

Sensor head

Default

value

Parameter range

Advertising