Chapter 14

OMM-0089_0A

Installation, Operation & Maintenance Manual Ext. Modulating Control

CHAPTER 14: EXTERNAL MODULATING CONTROL

The boiler can directly accept an analog 0-10VDC signal to control the firing rate from an

external modulating boiler controller.

14.1 WIRING THE EXTERNAL MODULATING CONTROLLER

Run two 18 gauge wires from the external modulating boiler controller’s 0-10 VDC boiler output

to the modulation signal terminals on the low voltage terminal strip inside the boiler (see boiler

wiring diagram, Figure 8-3). This signal will both enable and modulate the boiler. No wiring is

required at the thermostat terminals.

NOTE

Ensure that the polarity of the connections from the external

modulating controller to the boiler are correct. Reversed polarity will

lead to no response from the boiler.

14.2 EZ-SETUP CONTROLLER PROGRAMMING FOR EXTERNAL 0-
10V SIGNAL

The EZ-SETUP controller must be programmed to accept the 0-10 VDC signal from the external

modulating boiler control.
Refer to Section 10.6 for how to use the Heating EZ Setup function to set the CH Demand to 0-

10V Modulation Signal.

14.3 EXTERNAL PROGRAMMING OF 0-10V MODULATING CONTROL

The external modulating control must be programmed to send 2 VDC to enable the boiler and

run it at low fire, and 10 VDC to run the boiler at high fire. Once the control enables the boiler, it

must wait 30 seconds to allow the burner to stabilize before modulating the boiler.

IMPORTANT NOTE!

In accordance with Section 325 (f) (3) of the Energy Policy and

Conservation Act, this boiler is equipped with a feature that saves

energy by reducing the boiler water temperature as the heating

load decreases. This feature is equipped with an override which is

provided primarily to permit the use of an external energy

management system that serves the same function.

THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST
ONE OF THE FOLLOWING CONDITIONS IS TRUE.

An external energy management system is installed that

reduces the boiler water temperature as the heating load

decreases.

This boiler is not used for any space heating.

This boiler is part of a modular or multiple boiler system

having a total input of 300,000 BTU/hr. or greater.

This boiler is equipped with a tankless coil.

Page 103 of 188