Chapter 13: outdoor reset control, Chapter 13, Outdoor reset control – AERCO Esteem Boiler with EZ-Set Controller User Manual

Page 99

Advertising
background image

GF-135 Esteem 399 Low NOx Boiler

Chapter 13

OMM-0089_0A

Installation, Operation & Maintenance Manual Outdoor Reset Control

CHAPTER 13: OUTDOOR RESET CONTROL

The use of the outdoor reset function is required to optimize boiler efficiency. See the important

notice below.
If the outdoor sensor is not installed before turning on the boiler, an Outdoor Sensor Open error

(E96) will be displayed. The error will not prevent the boiler from operating. The error will

automatically reset once the outdoor sensor is installed or if the outdoor reset function is

disabled.
Reference section 10.6 for information on disabling the outdoor reset function using the EZ setup

menu. The outdoor reset function can only be disabled if the boiler installation meets one of the

exceptions listed in the following notice.

IMPORTANT NOTE!

In accordance with Section 325 (f) (3) of the Energy Policy and

Conservation Act, this boiler is equipped with a feature that saves

energy by reducing the boiler water temperature as the heating

load decreases. This feature is equipped with an override which is

provided primarily to permit the use of an external energy

management system that serves the same function.

THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST
ONE OF THE FOLLOWING CONDITIONS IS TRUE.

An external energy management system is installed that

reduces the boiler water temperature as the heating load

decreases.

This boiler is not used for any space heating.

This boiler is part of a modular or multiple boiler system

having a total input of 300,000 BTU/hr. or greater.

This boiler is equipped with a tankless coil.










Page 99 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14

Ph.: 800-526-0288

Advertising