AERCO Esteem Boiler with EZ-Set Controller User Manual

Page 104

Advertising
background image

GF-135 Esteem 399 Low NOx Boiler

Chapter 14

OMM-0089_0A

Installation, Operation & Maintenance Manual Ext. Modulating Control

Table 14-1: Esteem Boiler Factory Settings

Heating Settings

Factory Default EZ Setup Reset Installer Reset

Heating Operation

Enabled

Demand

Switch & Outdoor

Reset

Absolute Max CH Setpoint

194°F [90°C]

CH1 Maximum Setpoint

180°F [82°C]

CH1 Minimum Setpoint

120°F [49°C]

Reset Curve Coldest Day

0°F [-18°C]

Reset Curve Warmest Day

64°F [18°C]

CH2 Circuit

Enabled

CH2 Maximum Setpoint

140°F 60°C]

CH2 Minimum Setpoint

80°F [27°C]

Warm Weather Shutdown

OFF

Pump Constant Circulation

Disabled

CH Post Pump Time

1 minute

Freeze Protection

Enabled

Frost Protection Setpoint

-22°F [-30°C]

Parallel Shift Value

0°F [0°C]

CH Call Blocking

1 minute

System Pump

CH1/CH2

Domestic Settings

Factory Default EZ Setup Reset Installer Reset

DHW Operation

Enabled

Esteem Model

399

Demand

Switch

Boiler DHW Setpoint

186°F [86°C]

DHW Storage Setpoint

140°F [60°C]

DHW On Differential

6°F [3°C]

DHW Storage Adder

46°F [25°C]

DHW Post Pump Time

1 minute

DHW Priority Timeout

OFF

DHW Priority

Enabled

DHW Call Blocking

0 minute

DHW to CH Call Blocking

1 minute

Antilegionella Function

Disabled

Boiler Settings

Factory Default EZ Setup Reset Installer Reset

Lockout Temperature

210°F [99°C]

Modbus Address

0=BCST

Page 104 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14

Ph.: 800-526-0288