GF-135 Esteem 399 Low NOx Boiler

Chapter 18

OMM-0089_0A

Installation, Operation & Maintenance Manual Controller Operation

18.4.2 Demand Type (Default: Switch)

Figure 18-28: DEMAND TYPE Menu

Demand Type allows the installer to select the type of device which will generate a domestic hot

water call. Press the UP or DOWN buttons to select the DHW Demand Type then press the OK

button to store the set-ting. The DHW Demand options are:

Switch: A domestic hot water call from an aquastat or dry contact switch will enable the

Esteem with a fixed setpoint for a domestic hot water call.

Sensor: This option requires the use of Indirect Water Heater Sensor 69107, which is

included with every Esteem boiler. The Esteem will monitor the DHW storage temperature

and generate a domestic hot water call when the temperature drops below the DHW

Storage Setpoint - DHW On Differential.

========================================================================

18.4.3 Boiler DHW Setpoint (Default: 186°F [86°C])

Figure 18-29: BOILER DHW SETPOINT Menu

Boiler DHW Setpoint is the fixed boiler setpoint temperature during a domestic hot water call

when the Switch option is chosen in DHW Demand. Press the LEFT or RIGHT buttons to adjust
the Boiler DHW Setpoint then press the OK button to store the setting.

18.4.4 DHW Storage Setpoint (Default: 140°F [60°C])