GF-135 Esteem 399 Low NOx Boiler

Chapter 18

OMM-0089_0A

Installation, Operation & Maintenance Manual Controller Operation

18.5 BOILER SETTINGS MENU

Navigation: Home Screen > Installer Menu > CH & DHW Settings > Boiler Settings








INSTALLER Menu CH & DHW SETTINGS Menu BOILER SETTINGS Menu

Figure 18-39: Navigation to the BOILER SETTINGS Menu

The Boiler Settings menu contains settings related to general boiler operation. Each line contains a Boiler

Setting followed by its current value.

========================================================================

18.5.1 Lockout Temp (Default: 210°F [99°C])

Lockout Temp. allows the High Boiler Temperature lockout (E3) to be temporarily adjusted down

to 102°F [39°C] for inspector demonstration. Press the UP or DOWN buttons to select 210°F

[99°C] or 102°F [39°C], then press the OK button to store the setting.

Figure 18-40: LOCKOUT TEMP. Menu

102°F [39°C]: A High Boiler Temperature lockout (E3) will occur when the boiler temperature

reaches 102°F [39°C].

210°F [99°C]: A High Boiler Temperature lockout (E3) will occur when the boiler temperature

reaches 210°F [99°C].


Page 143 of 188