4 alarm wiring, 5 low voltage connections, 6 thermostat wiring – AERCO Esteem Boiler with EZ-Set Controller User Manual

Page 57

Advertising
background image

GF-135 Esteem 399 Low NOx Boiler

Chapter 9

OMM-0089_0A

Installation, Operation & Maintenance Manual External Wiring

9.4 ALARM WIRING

The alarm contact closes whenever the Esteem is in a soft or hard lockout. This dry contact can

be connected to an external monitoring system or other indicator to alert the operator that the

Esteem is locked out.
Connect the external monitoring device to the line voltage terminal strip on the wiring panel

below the Esteem control module, as shown in Figure 8-3.

NOTE

The alarm contact is fused with a 2.5A fuse located in the terminal

strip. An isolation relay is required if the external monitoring device

draws more than 2.5A.

9.5 LOW VOLTAGE CONNECTIONS

Line and Low Voltage wiring should be separated to prevent possible electrical noise on the low

voltage circuits. Line and Low Voltage wiring should use separate electrical knockouts on the

Esteem cabinet and should remain separated inside the Esteem.
CH and DHW call connections to the Esteem require a dry contact with no external voltage

present. Ensure no external voltage is present on each set of wires before connecting to the

Esteem. If external voltage is present, the use of an isolation relay is required to prevent

damage to the Esteem EZ-SETUP controller.

9.6 THERMOSTAT WIRING

The Esteem EZ-SETUP Controller has two thermostat call inputs for multiple zone / temperature

systems. This allows each call to have its own outdoor reset curve and maximizes the efficiency

of the system.

WARNING!

Simultaneous CH1 and CH2 calls will result in the Esteem boiler

operating at the highest target temperature. The use of a mixing

device on the lower temperature zones may be required to protect

the lower temperature zones from damage.

Wire a thermostat to the Esteem unit as follows.

Wiring the Thermostat to the Esteem Boiler

1. Connect the room thermostat or dry contact end switch to the low voltage terminal strip on

the wiring panel below the Esteem control module, as shown in Figure 8-3.

2. Follow thermostat manufacturer’s instructions for proper installation. Thermostat should be

located on an inside wall away from any heat or cold influences such as drafts, lights,

fireplaces, etc.

3. Set the thermostat anticipator (If applicable) as follows:

Set for 0.2 amps when wired directly to the Esteem.

Set to match the electrical power requirements of the connected device when wired to

zone relays or other devices. Refer to the relay manufacturer’s specifications and the

thermostat instructions for additional information on anticipator setting.

Page 57 of 188