GF-135

Esteem 399 Low NOx Boiler

Chapter 2

OMM-0089_0A

Installation, Operation & Maintenance Manual

Combustion Air/Venting

3.5.1 INDOOR COMBUSTION AIR

Openings used to connect indoor spaces shall be sized and located in accordance with

Figure 3-1.

Figure 3-1: All Combustion Air from Adjacent Indoor Spaces Through Indoor

Combustion Openings

Each opening shall have a minimum free area of 1 sq. in./1000 Btu/hr. of the total input rating of

all gas utilization equipment in the space, but not less than 100 sq. inches. One opening shall

commence within 12 inches of the top, and one opening shall commence within 12 inches of the

bottom of the enclosure. The minimum dimension of air openings shall be not less than 3

inches.
Combining spaces in different stories. The volumes of spaces in different stories shall be

considered as communicating spaces where such spaces are connected by one or more

openings in doors or floors having a total minimum free area of 2 sq. in./1000 Btu/hr. of total

input rating of all gas utilization equipment.




Page 22 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14