GF-135 Esteem 399 Low NOx Boiler

Chapter 18

OMM-0089_0A

Installation, Operation & Maintenance Manual Controller Operation

18.7.5 Cascade Installation – Line Voltage Wiring Connections

Circulator Wiring: Reference Figures 18-45, 18-47, and 18-49 for circulator wiring required

for each type of Cascade System. The circulator connections used will depend on the

systems piping layout.

NOTE

Each circulator is individually fused with a 2.5A fuse located in the

terminal strip. The total combined amp draw of the CH (1), DHW,

and auxiliary Boiler circulators must not exceed 3 amps at any time

for the Esteem boiler. Use an isolation relay to lower the total

combined amp draw if exceeding these limits.

Power Supply: A dedicated 120 VAC / 15A minimum service must be used to power the

boilers in the Cascade System. Multiple boilers in the Cascade System can be placed on

the same electrical circuit. Each boiler can draw a maximum of 8 amps.

Alarm Wiring: The alarm contact closes whenever that particular boiler is in a soft or hard

lockout. The alarm contact will also close on the Master boiler when any of the Slave

boilers are locked out.

























Page 150 of 188

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0089_0A

MC1 06/19/14